China Rules For Economic & Environmental-friendly Industrial Boiler Output Smoke-gas
Considering Boiler Safety and Boiler Economic Running, Normally, When Design Boiler, Output Smoke Temperature Should Obey Regulation As Following:
Smoke Temperature Should Obey Regulation As Following:
Steam Boiler <1ton, Exhaust Smoke Temperature <230°C
Hot Water Boiler <0.7mw, Exhaust Smoke Temperature <180°C
Steam Boiler>1ton & Hot Water Boiler>0.7mw, Exhaust Smoke Temperature <170°C
Thermal Oil Boiler>1.4mw, Exhaust Smoke Temperature <170°C